B300 delivery: have you finished 45 checks, including a 30-minute burn, before you sign?

Essential acceptance inspection for NVIDIA B300 GPU deliveries — 45 checks across 5 phases to protect against shipping damage, defaults, and warranty disputes.

Quick Take

Quick Take: Accepting a DGX B300 crate without a written inspection is how buyers inherit transit damage as their own warranty problem. Forty-five checks across five phases, from crate photographs through a thirty-minute burn test, decide whether you sign for the delivery or send it back.

Phase 1: Pre-Inspection Preparation

Quick Answer: Half an hour of preparation with one logistics staffer and one technician. Match serial numbers to the purchase order, photograph every face of each crate along with its shock indicators, set up an ESD-safe bench, and boot the diagnostic USB on a known-good machine so tooling failures cannot masquerade as hardware faults.

Phase 1: Pre-Inspection

Time: 30 min | Staff: 1 logistics + 1 technician

1
Verify shipping manifestCritical
Match model number, quantity, and serial numbers against purchase order. Any discrepancy stops inspection until resolved.
2
Document crate conditionCritical
Photograph all 6 sides of every crate before opening. Log shock/vibration indicators. Note any damage signs.
3
Prepare inspection areaMedium
ESD-safe flooring, adequate lighting, clean table surface, calibrated tools ready.
4
Prepare diagnostic toolsHigh
Pre-load USB boot drive with DCGM, nvidia-smi, gpu_burn, memtest_cuda, and firmware check scripts. Verify tools work on a known-good system first.
5
Verify delivery paperworkMedium
Inspection report template printed. Warranty registration forms ready. RMA process documented.

Phase 2: Physical Inspection

Quick Answer: One to two hours with two technicians on the mechanical state of a 168 kg chassis. The critical items are the GPU retention latches and NVSwitch seating, because transit damage there surfaces later as an intermittent link rather than a dead card. Everything else is dents, fasteners, fans, and bent pins.

Phase 2: Physical Inspection

Time: 1-2 hours | Staff: 2 technicians

6
Open crate and remove packing materialCritical
Use proper tools. Do not tilt or drop. Two-person lift required — DGX B300 is 168 kg.
7
Inspect chassis exteriorHigh
Check for dents, scratches, bent metal, rack rail misalignment. Photograph any defects.
8
Check all panel screws and fastenersMedium
Verify no screws are missing, stripped, or cross-threaded. Torque-check accessible fasteners.
9
Inspect GPU module retention latchesCritical
Open and close each latch. Verify smooth engagement. Damaged latches = risk of GPU seating failure during transit.
10
Inspect NVSwitch module seatingCritical
Verify NVSwitch is fully seated. Check alignment pins and locking mechanism. Photo for records.
11
Check fan assembly and rotationMedium
Manually spin each fan. Listen for grinding or scraping. Fan should spin freely for 3+ rotations.
12
Inspect PCIe slots and risersHigh
Visually check for bent pins, debris, or damage. Verify NICs are properly seated.
13
Check rear I/O panelMedium
Verify all ports are present and undamaged. Check for bent pins in USB, RJ45, and QSFP ports.

Phase 3: GPU and Component Verification

Quick Answer: Nine checks build the asset record. Log all eight GPU serial numbers against the manifest and the warranty database, confirm eight ConnectX-8 adapters and the power supply count, then verify DIMM retention, NVMe population, and that every quick-disconnect coolant fitting is fully engaged and free of residue.

Phase 3: Component Verification

Time: 1-2 hours | Staff: 2 technicians

14
Record all GPU serial numbersCritical
Log all 8 GPU serial numbers per DGX B300. Cross-reference against shipping manifest and NVIDIA warranty database.
15
Verify GPU module labelsHigh
Confirm GPU module model labels match B300 specification. Check manufacturing date codes.
16
Log PSU model and quantityHigh
DGX B300 has 2+ PSUs. Verify model, power rating, and firmware compatibility.
17
Inspect all cable bundlesMedium
Check for kinks, cuts, crushed sections, or damaged connectors. Pay special attention to fiber optic cables.
18
Verify InfiniBand/Ethernet NICsHigh
Match NIC model and firmware label against PO. Verify 8x ConnectX-8 per DGX B300.
19
Check all memory module seatingHigh
Verify DIMMs fully seated, retention clips engaged. Document any popped or loose modules.
20
Inspect storage drivesMedium
Verify NVMe drive count and model. Check for proper seating in backplane.
21
Verify accessory kit completenessMedium
Check rail kits, cable management arms, power cables, documentation. Match against packing list.
22
Check liquid cooling loop connection pointsCritical
Verify QD (quick-disconnect) fittings are fully engaged. Look for any coolant residue.

Phase 4: Cooling and Power Validation

Quick Answer: An hour with facility staff present. Confirm the house coolant loop matches specification, hold a pressure test for thirty minutes, check that supply voltage matches the power supply rating before energizing anything, and measure chassis-to-building ground continuity below one ohm. Wrong input voltage destroys supplies instantly.

Phase 4: Cooling & Power

Time: 1 hour | Staff: 2 technicians + facility

23
Verify CDU connection compatibilityCritical
Confirm facility CDU loop matches B300 coolant specifications. Check flow rate and temperature range.
24
Pressurize liquid cooling loopCritical
Perform pressure test per NVIDIA specification. Hold pressure for 30 minutes. Document results.
25
Inspect RDHx mountingHigh
Verify active rear-door heat exchanger is properly mounted and plumbed. Check for leaks.
26
Check PSU input voltage and frequencyCritical
Verify facility power matches PSU rating. Wrong voltage causes immediate PSU failure.
27
Test PSU power-on (no GPU load)High
Connect power, verify PSU indicator lights. Each PSU should show green status LED.
28
Verify ground continuityCritical
Measure resistance between chassis ground and facility ground. Must be < 1 ohm.
29
Check thermal interface materialMedium
Verify TIM pads between GPU and cold plate are present and undamaged (visible through access panels).

Phase 5: Power-On and Acceptance Testing

Quick Answer: Four to eight hours of loaded testing decides acceptance. All eight GPUs must survive a thirty-minute burn at 1,400 W each while staying under 85 degrees, all 18 NVLink bridges must report active, and node-local all-reduce should clear 100 GB/s. Any ECC error at delivery is grounds for return.

Phase 5: Acceptance Testing

Time: 4-8 hours | Staff: 2 engineers

30
System power-on testCritical
Boot system to BIOS. Verify POST completes without errors. Log any beep codes or error messages.
31
Check BMC/iLO/iDRAC functionalityHigh
Verify remote management interface is accessible. Check sensor readings (temp, voltage, fan speed).
32
Verify BIOS versionHigh
Record BIOS version. Compare against NVIDIA B300 BIOS compatibility matrix. Update if needed.
33
Log all GPU firmware versionsCritical
Run nvidia-smi -q and record all firmware versions. Cross-check against NVIDIA's latest recommended versions.
34
NVSwitch firmware checkCritical
Verify NVSwitch firmware version matches NVIDIA spec. This is a common mismatch — 8% of deliveries.
35
Boot to OSHigh
Boot from USB or PXE. Verify OS detects all 8 GPUs via nvidia-smi.
36
Run GPU ECC memory testCritical
Run cuda_memtest or memtest_cuda on all 8 GPUs. Any ECC errors at delivery = RMA.
37
Run GPU burn test (30 min)Critical
Run gpu_burn for 30 minutes. Verify all GPUs reach full TDP (1,400W) without thermal throttling.
38
Verify GPU temperature stabilityHigh
Under full load, GPU temp must stabilize below 85°C. Log max temp per GPU.
39
Run NVLink connectivity testCritical
Use nvidia-smi topo -m to verify NVLink topology. All 18 NVLink bridges must show active.
40
Run NCCL bandwidth benchmarkHigh
Run nccl-tests all_reduce_perf. Expected 100+ GB/s for 8-GPU within-node all-reduce.
41
Verify NIC link statusHigh
Check all ConnectX-8 links at expected speed. Verify InfiniBand/Ethernet link training.
42
Liquid cooling loop leak test at loadCritical
After temperature stabilizes under load, inspect all QD fittings and hose connections for any moisture.
43
Power draw verificationMedium
Under full load, verify total system power draw is within spec (approximately 8-11kW per DGX B300).
44
Comprehensive firmware and log archiveHigh
Save all diagnostic output to external media. This is your baseline for future warranty claims.
45
Sign off or escalateCritical
If all checks pass: sign delivery acceptance, register warranty, deploy to production. If any critical or high check fails: document findings, notify supplier, do NOT sign acceptance.

When to Refuse Delivery

Quick Answer: Seven conditions justify turning the truck around rather than accepting and filing a claim later. Structural crate or chassis damage, a damaged GPU latch, any coolant leak under pressure, two or more GPUs reporting hardware memory errors, a failed NVSwitch link test, or a dead POST all warrant refusal.

Automatic Rejection Criteria

  • Crate shows major physical damage with potential internal impact
  • Visible chassis deformation or structural damage
  • GPU module retention latch damage (risk of loose GPU during operation)
  • Liquid cooling loop showing signs of leakage during pressure test
  • More than 1 GPU (out of 8) showing hardware ECC errors during diagnostic tests
  • NVSwitch fails connectivity test (all 18 links must be active)
  • System fails POST or BMC is unresponsive

Documentation Checklist

Quick Answer: Seven artifacts form the evidence pack behind any future warranty claim: photographs of every crate face, four views of each chassis, the serial register, a firmware dump, raw diagnostic output from the memory and burn tests, the thermal trace recorded under load, and the countersigned report.

Save the following for every delivery: crate photos (6 sides per crate), chassis photos (front, rear, top, bottom), GPU serial number log, firmware version dump, diagnostic test output (nvidia-smi, gpu_burn, cuda_memtest, nccl-tests), temperature log under load, and signed inspection report.

Frequently Asked Questions

Quick Answer: Five questions cover scope, duration, the defect distribution, refusal thresholds, and outside help. Budget four to six hours per system for the 45 checks, and expect the defect mix to be led by GPU seating damage near 15 percent and coolant connector misalignment around 12 percent.

Follow the 45-point checklist: pre-inspection, physical inspection, GPU verification, cooling validation, and power-on testing. Takes 4-6 hours per DGX B300 system.

4-6 hours per DGX B300 system, 8-12 hours for a rack (4 systems), with 2 technicians per system. Power-on and stress testing adds 4-8 hours.

GPU module seating damage (15%), liquid cooling connector misalignment (12%), NVSwitch firmware mismatch (8%), missing accessories (5%), GPU ECC errors at delivery (3%).

Refuse if: major crate damage, chassis deformation, GPU latch damage, cooling loop leakage, more than 1 GPU with hardware errors, NVSwitch failure, or system fails POST.

BENQUAN GLOBAL LIMITED provides third-party B300 delivery inspection services at our free-port logistics hub. Contact info@benquan.hk for on-site acceptance testing support.

Key Takeaway: Sign nothing until all eight GPUs clear the memory test and every NVLink bridge reports active; a single ECC error or a weeping quick-disconnect is an RMA, not a punch-list item. BENQUAN GLOBAL LIMITED supplies NVIDIA DGX B300 systems with competitive pricing and acceptance-testing support.

Not sure your BOM is optimal?

If you are unsure whether your BOM is optimal, click below for a free compatibility and delivery risk assessment. Fast global BOM validation and risk assessment.